7 software update procedure, Software update procedure – Lenze PC-based Automation Industrial PC User Manual
Page 73
2.5 EN - 01/2012
L
73
Industrial PC | Parameter setting & configuration
IPC backup & restore
Software update procedure
9.7
Software update procedure
Steps to be carried out in the case of R1.5:
How to identify the currently installed version:
In the web-based parameterisation the software version can be found under:
• Parameter list 1 -> Device: Software version
• The first two version numbers are important.
Carrying out a SW update of R1.5
When you install an update of R1.5, e. g. to R2.0, you have to carry out the following steps:
How to carry out an R1.5 software update:
1. Prepare USB stick for an update with »IPC Backup & Restore« under Windows® XP.
2. Connect USB stick to the running Industrial PC
3. Copy the BackupRestoreX86Rel.Cab from directory
\USBStorage\
to
\Storage\BackupRestoreX86Rel.Cab under Windows® CE.
4. Remove USB stick.
5. Restart Industrial PC.
• By this the new runtime environment is extracted.
6. Restart Industrial PC with the USB stick prepared.
Note!
Lenze recommend archiving the Compact Flash card using »IPC Backup &
Restore« under Windows® XP before carrying out a software update.