Industrial pc | parameter setting & configuration – Lenze PC-based Automation Industrial PC User Manual
Page 203

2.5 EN - 01/2012
L
203
Industrial PC | Parameter setting & configuration
Parameter reference
Industrial PC extension modules
C1596/20
C1596/21
C1596/22
0x0043
MBX_COE
B, P, S, O
Current state + E
0x0044
MBX_FOE
B, P, S, O
Current state + E
0x0045
MBX_SOE
B, P, S, O
Current state + E
0x004F
MBX_VOE
B, P, S, O
Current state + E
Code (hex)
Description
Current state or state
change
Resulting state
Legend:
I: Initialisation
B: Bootstrap (is not supported)
P: Pre-Operational
S: Safe Operational
O: Operational
E: Error-Flag
Parameter | Name:
C1596/20 | ECAT: Active sync pulse
Data type: UNSIGNED_8
Index: 22979.20
d
=
0x59C3.0x14
h
• Value "0": Sync pulse of distributed clocks not activated on the slave.
• Value "1": Sync pulse of distributed clocks activated on the slave.
Display range
(min. value | unit | max. value)
0
1
;
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1596/21 | ECAT: DC sync 0 period
Data type: UNSIGNED_32
Index: 22979.21
d
=
0x59C3.0x15
h
Period in which setpoints are expected to be received from the control system if the distributed clocks support has
been switched-on.
Display range
(min. value | unit | max. value)
0
4294967295
;
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1596/22 | ECAT: DC sync 1 period
Data type: UNSIGNED_32
Index: 22979.22
d
=
0x59C3.0x16
h
Distributed clocks sync 1 period
Note: At present, distributed clocks are not used on the sync 1 of Lenze slaves.
Display range
(min. value | unit | max. value)
0
4294967295
;
Read access Write access CINH PLC STOP No transfer