Industrial PC | Parameter setting & configuration

Parameter reference

Parameters of standard devices

132

L

2.5 EN - 01/2012

C0040

C0041

C0042

C0048

C0049

C0050

Parameter | Name:

C0040 | Activate front USB

Data type: UNSIGNED_8

Index: 24535

d

= 5FD7

h

The optional USB socket located on the front monitor panel is

• activated by entering "1" and

• deactivated by entering "0".
Setting range

(min. value | unit | max. value)

Lenze setting

0

1 0

;

Read access ; Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C0041 | Operating time

Data type: UNSIGNED_32

Index: 24534

d

= 5FD6

h

Total operating time since the device has been switched on [s]
Display range

(min. value | unit | max. value)

0

min

16777215

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C0042 | Number of reboots

Data type: UNSIGNED_32

Index: 24533

d

= 5FD5

h

Number of boot processes of the device
Display range

(min. value | unit | max. value)

0

65535

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C0048 | Logbook: Time to auto persist

Data type: UNSIGNED_32

Index: 24527

d

= 5FCF

h

The time for the timer is entered in minutes. The timer is restarted when the log service has saved data. If the time

has expired and no logbook entries have been saved in the meantime, the saving process will be activated.
Setting range

(min. value | unit | max. value)

Lenze setting

min

2 min

;

Read access ; Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C0049 | Logbook: Entry count to auto persist

Data type: UNSIGNED_32

Index: 24526

d

= 5FCE

h

Enter the number of logbook entries after which the saving process is to be activated. Counting starts with the last

saving.
Setting range

(min. value | unit | max. value)

Lenze setting
900

;

Read access ; Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C0050 | Logbook: Max. entries

Data type: UNSIGNED_32

Index: 24525

d

= 5FCD

h

Enter the maximum number of logbook entries. The logbook entries are taken from the main memory and from the

CF memory card.
Setting range

(min. value | unit | max. value)

Lenze setting
1000

;

Read access ; Write access … CINH … PLC STOP … No transfer