Industrial PC | Parameter setting & configuration
Parameter reference
Industrial PC extension modules
C1586/14
C1595/1
C1595/2
C1596/1
Parameter | Name:
C1586/14 | ECAT: Reset individual counters
Data type: UNSIGNED_32
Index: 22989.14
d
=
0x59CD.0x0E
h
Reset frame and datagram counters (C1586/7 ... 13)
Selection list
(Lenze setting printed in bold)
0 No action
1 Reset - All counters
2 Reset - Tx frame counters
4 Reset - Rx frame counters
8 Reset - Lost frame counters
16 Reset - Cyclic frame counters
32 Reset - Cyclic datagram counters
64 Reset - Acyclic frame counters
128 Reset - Acyclic datagram counters
;
Read access ; Write access CINH PLC STOP ; No transfer
Parameter | Name:
C1595/1 | ECAT: Slave addressing mode
Data type: UNSIGNED_8
Index: 22980.1
d
=
0x59C4.0x01
h
The addressing mode refers to the slave address (
C1595/2
).
Selection list
(Lenze setting printed in bold)
0 Position addressing
Auto increment addresses:
The addresses depend on the position of the respective
slave in the EtherCAT bus (i.e. 0, -1, -2, ...).
1 Node addressing
Physical addresses:
The addresses are assigned consecutively by the »PLC
Designer« (i.e. 1001, 1002, ...)
;
Read access ; Write access CINH PLC STOP ; No transfer
Parameter | Name:
C1595/2 | ECAT: Slave address
Data type: INTEGER_32
Index: 22980.2
d
=
0x59C4.0x02
h
Use this code to select a slave whose parameters are to be displayed.
The addressing mode is specified in code
C1595/1
. A maximum of 4096 slaves can be addressed after the master.
Setting range
(min. value | unit | max. value)
-65536
65536
;
Read access ; Write access CINH PLC STOP No transfer
Parameter | Name:
C1596/1 | ECAT: Valid entry
Data type: UNSIGNED_8
Index: 22979.1
d
=
0x59C3.0x01
h
This code indicates whether the entries/values of the following subcodes C1596/2 ... /38 are valid or not.
• Value "0": Invalid entry/value
• Value "1": Valid entry/value (The parameters of an available slave are displayed.)
Display range
(min. value | unit | max. value)
0
1
;
Read access Write access CINH PLC STOP No transfer