Industrial PC | Parameter setting & configuration

Parameter reference

Parameters of standard devices

C0208

C0209

C0210

C0211

C0212

C0213

Parameter | Name:

C0208 | UPS: Display light after volt. fail.

Data type: UNSIGNED_8

Index: 24367

d

= 5F2F

h

Selection list

(Lenze setting printed in bold)

Information

0 OFF
1 On

;

Read access ; Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C0209 | UPS: Number of voltage dips

Data type: UNSIGNED_8

Index: 24366

d

= 5F2E

h

Display range

(min. value | unit | max. value)

0

255

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C0210 | UPS: Supply voltage OK

Data type: UNSIGNED_8

Index: 24365

d

= 5F2D

h

Selection list

(read only)

Information

0 No
1 Yes

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C0211 | UPS: Voltage failure

Data type: UNSIGNED_8

Index: 24364

d

= 5F2C

h

Selection list

(read only)

Information

0 No
1 Yes

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C0212 | UPS: Firmware version

Data type: VISIBLE_STRING

Index: 24363

d

= 5F2B

h

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C0213 | UPS: Buffer time without action

Data type: UNSIGNED_16

Index: 24362

d

= 5F2A

h

The UPS buffers the system without further action. If the voltage dip takes longer than the time set here:

• The PLC is stopped.

• The PLC saves the retain variables, logbook entries and visualisation data (trends and alarms).

• The timer

C00214

is started.

Selection list

(Lenze setting printed in bold)

Information

0 0

250 250
500 500
750 750

1000 1000
1250 1250
1500 1500
1750 1750
2000 2000
2250 2250