Industrial pc | parameter setting & configuration – Lenze PC-based Automation Industrial PC User Manual
Page 201
2.5 EN - 01/2012
L
201
Industrial PC | Parameter setting & configuration
Parameter reference
Industrial PC extension modules
C1596/17
C1596/18
Selection list
(read only)
0 Unknown
1 Init
2 Pre-Operational
4 Safe Operational
8 Operational
;
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1596/16 | ECAT: Current state
Data type: UNSIGNED_32
Index: 22979.16
d
=
0x59C3.0x10
h
Parameter | Name:
C1596/17 | ECAT: Active error
Data type: UNSIGNED_8
Index: 22979.17
d
=
0x59C3.0x11
h
• Value "0": No error
• Value "1": An error is active
Display range
(min. value | unit | max. value)
0
1
;
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1596/18 | ECAT: Activate link messages
Data type: UNSIGNED_8
Index: 22979.18
d
=
0x59C3.0x12
h
Debug parameter:
If the parameter is set to value "1", all state changes of the slave will be output in the form of a diagnostic frame via
the Ethernet interface. In the event of an error, a wireshark record can be used for error diagnostic purposes.
(»Wireshark«: Program for the analysis of network communication links)
• Value "0": No link messages
• Value "1": Activate link messages
Setting range
(min. value | unit | max. value)
Lenze setting
0
1 0
;
Read access Write access CINH PLC STOP No transfer