beautypg.com

3 interconnect modules are in unmanaged state – HP OneView User Manual

Page 246

background image

31.10.3 Interconnect modules are in Unmanaged state

Possible cause and recommendation

Symptom

Interconnect bay has a mismatch with the expected type

The logical interconnect group is expecting a different interconnect than what is in the enclosure.

Use the expected interconnect:
1. Remove the enclosure from the Enclosures screen.
2. Insert the expected interconnect into the enclosure.
3. Add the enclosure on the Enclosures screen.

Use the actual interconnect by updating the logical interconnect group.

Interconnect modules
are in an Unmanaged
state

Interconnect has firmware installed which is less than the minimum supported baseline version

For an HP Virtual Connect Fibre Channel interconnect:

The enclosure contains an HP Virtual Connect Fibre Channel interconnect with IPv6
addresses and the interconnect firmware version is less than 4.10, the minimum supported
baseline version.

The enclosure contains only an HP Virtual Connect Fibre Channel interconnect by itself
or with other HP Virtual Connect Fibre Channel interconnects and the interconnect
firmware version is less than 4.10, the minimum supported baseline version.

Recommendation
1. Remove the enclosure from the Enclosures screen.
2. Update the interconnect firmware for HP Virtual Connect Fibre Channel interconnects as

described in the online help.

3. Add the enclosure on the Enclosures screen.

For an interconnect that is not an HP Virtual Connect Fibre Channel, update the interconnect
firmware for the logical interconnect as described in the online help.

246 Troubleshooting