IAI America PCON-CF User Manual

Page 51

background image

33

4. W

iring

4.2.2

Wiring the Power Supply/Emergency-Stop Switch

(1)

Wiring the power supply

To connect multiple controllers, provide a relay terminal block.
Use a power cable satisfying the following specifications:

Item Specification

Applicable wire length

Single wire:

‡1.0 / Stranded: 0.8 mm

2

, AWG size 18, (copper wire)

Stripped wire length

10 mm

Temperature rating of
isolated sheath

60

qC or above

* Use a flathead screwdriver with a blade tip of approx. 2.6 mm to push in the wire.

S1
S2
MPI
MPO
24V
0V
EMG-

24V

0V
FG

Input power supply
24 VDC

(2 A max. per controller)