90

7. Operation

Home return operation

Home position

Mechanical end

Power on p

o

sition

Emergency stop not actuated (motor drive power supplied)

Safety circuit condition

Supply of
24-VDC I/O power

Supply of 24-VDC
controller power

Servo ON
operation

Monitor LED
[SV/ALM]

Ready (SV)

An orange light
comes on initially
for 2 seconds and
then turns off.

Initial parameter
settings

Green

Set a target position in the “Position” field of the
position table via PC or teaching pendant operation
Also set optimal values for other items.

T1 (Note 1)

[10] Perform home return.

z Overview of operation on the teaching pendant

x On the RCM-T, select the “Edit/Teach” screen, bring the cursor to “*Home” in the sub display area,

and then press the Return key.

x On the RCM-E, select the “Teach/Play” screen, scroll until “*Home Return” is displayed, and then

press the Return key.

[11] Set a target position in the “Position” field of the position table.

Set a target position in the “Position” field of each position table.
Determine a desired target position by fine-adjusting the load and hand via jogging or inching.
Also adjust the servo gain, if necessary.
* Once a target position has been set, other fields (speed, acceleration/deceleration, positioning band,

etc.) will be automatically populated by their default values. Set optimal values for the speed,
acceleration/deceleration, positioning band, etc.

* For safety reasons, it is recommended that the safety speed be enabled during the initial movement.

To move the actuator at the actual speed set in the “Speed” field of the position table, change the MANU
operation mode to [Teaching mode: Disable safety speed].

(Note 1) T1: Excited-pole detection time = 0.2 to 12 sec

Normally the detection of excited pole completes in approx. 0.2 sec, although the exact time varies from one
actuator to another due to individual differences and also depending on the load condition. If the detection of
excited pole has failed, the excited-pole detection operation will be continued for up to 12 sec.