8. Parameter Settings

z Speed loop integral gain (No.32 VLPT)

Parameter

No. Unit Input

range

Default

32

---

1 ~ 217270

Set individually in accordance with the

actuator characteristics.

z Torque filter time constant (No.33 TRQF)

Parameter

No. Unit Input

range

Default

33

---

1 ~ 2500

Set individually in accordance with the

actuator characteristics.

This parameter determines the filter time constant for torque commands.
If the resonance frequency of the machine is smaller than the response frequency of the servo loop, the motor
vibrates.
This mechanical resonance can be suppressed by increasing the value set in this parameter.
However, increasing the parameter value excessively may reduce the stability of control.

This parameter determines the level of response with respect to a speed control loop.
Decreasing the setting results in lower response to the speed command and decreases the reactive
force upon load change. If the setting is too low, compliance with the position command drops and the
positioning time increases as a result.
Increasing the setting too much increases the tendency of the actuator to overshoot or oscillate,
resulting in increased mechanical vibration.

Speed

Setting is low

Setting is high (overshoot)

Time