8. Parameter Settings
8.2.3
Parameters Relating to the External Interface
z PIO pattern selection (No.25 IOPN)
Select the PIO operation pattern in parameter No. 25. 
This setting forms the basis of operation, so be sure to set this parameter at the beginning. 
The factory setting is “0 [Standard type].” 
Parameter No.
25 setting
Feature of PIO pattern
0
Standard type 
A basic type supporting 64 positioning points and two zone outputs. 
* How to set zone boundaries within which to output a zone signal: 
Zone boundaries are set using parameter Nos. 1 and 2 for one zone output, and in the 
position table for another zone output. 
1
Teaching type 
In this type, 64 positioning points and one zone output (boundaries are set in the 
position table) are supported. 
In addition to the normal positioning mode, the user can also select the teaching mode 
in which the actuator can be jogged via commands from a PLC and the current actuator 
position can be written to a specified position. 
(Note 1) Jog commands from a PLC are also accepted in the positioning mode. 
(Note 2) Positions can be rewritten by approximately 100,000 times. 
2
256-point positioning type 
The number of positioning points is increased to 256, so only one zone output is 
available (boundaries are set in the position table). 
3
512-point positioning type 
The number of positioning points is increased to 512, so no zone output is available. 
4
7-point type 
The number of positioning points is limited to seven to offer separate direct command 
inputs and movement complete outputs for respective positions. 
PLC ladder sequence circuits can be designed easily. 
5
3-point type 
Use of the controller as an air cylinder is assumed in this type. 
Movement complete output signals function differently in this type, compared to the 7-
point type. 
Specifically, the signal functions not only to “indicate movement complete,” but also to 
“detect a position” in the same manner as auto-switches of an air cylinder. Push & hold 
operation cannot be performed. 