27

4. W

iring

Representative connection examples are explained below.
z Connecting the teaching pendant directly to the controller

[1] Connecting multiple controllers (8 units or less) using a single power supply
x Short the MPI and MPO terminals using a jumper wire. (The controller is shipped with these terminals

shorted.)

x Connect one end of the EMG signal to the 24-V output of the input power supply and the other end to the S1

terminal.

Then, provide connections by sequentially connecting the S2 terminal of controller 1 to the S1 terminal of
controller 2, the S2 terminal of controller 2 to the S1 terminal of controller 3, and so on, and connect the S2
terminal on the last controller to the EMG terminals on all controllers.
Use a relay terminal block for connection to the EMG terminals.
(Note) Do not connect two or more wires to one terminal.