7. Operation

7.12 Operation in 3-point Type

After the power has been turned on, input the rear end move command first to complete home return, and then
perform continuous operation.
o Refer to 7.2.2, “Method Used When No HOME Input Signal Is Available.”
Example of use in operation) How to move the actuator from the rear end to the front end is explained.

Although the actuator does not stop at the intermediate point, you can increase
the positioning band and use the intermediate point detected output signal (LS2)
as a quasi zone output signal.

Example of position table

No.

Position

[mm]

Speed

[mm/s]

Acceleration

[G]

Deceleration

[G]

Push

[%]

Positioning

band [mm]

Remarks

0

5.00

300.00

0.30 0.30 0

0.10

Rear

end

1

380.00

300.00

0.30 0.30 0

0.10

Front

end

2

200.00

300.00

0.30 0.30 0

50.00

Intermediate

point

Operation timings

PLC processing 1: Turn OFF the rear end move command signal (ST0) and intermediate point move command

signal (ST2), and turn ON the front end move command signal (ST1).

Operation:

[1] The actuator starts moving toward the front end.
[2] When the current position passes 5.1 mm, the rear end detected output (LS0) turns OFF.
[3] When the current position reaches 150 mm, the intermediate point detected output (LS2)

turns ON. Once 250 mm is passed, LS2 turns OFF.

PLC processing 2: If necessary, use the intermediate point detected output (LS2) as a trigger signal with respect

to surrounding equipment.
[4] When the current position reaches 379.9 mm, the front end detected output (LS1) turns

ON.

[5] When the current position reaches 380 mm, the actuator stops.

PLC processing 3: Once the front end detected output (LS1) turns ON, the sequence processing at the front end

is executed. Upon completion of the sequence processing, the front end move command
signal (ST1) turns OFF.

Caution: Provide a ladder sequence circuit where only one move command signal turns ON at a

time. If two or more signals are input at the same time, the signals will be processed in the
following priorities:
Priorities: [1] Rear end, [2] Front end, [3] Intermediate point

365 mm

0.2 mm

100 mm

0.2 mm

Front end move command input

(ST1)

Rear end detected output

(LS0)

Intermediate point detected output

(LS2)

Front end detected output

(LS1)

Speed

Rear end:

5 mm

Intermediate point:

200 mm

Front end:

380 mm

Execution of
sequence at
the front end

Time