4 heat radiation and installation – IAI America PCON-CF User Manual

Page 41

background image

23

3. Installation and Noise Elimination

3.4

Heat Radiation and Installation

Design the control panel size, controller layout and cooling method in such a way that the temperature around
the controller will not exceed 40

qC.

Install the controller vertically on a wall, as shown below. Since cooling is provided by way of natural convection,
always observe this installation direction and provide a minimum clearance of 50 mm above and below the
controller to ensure sufficient natural airflows.

When installing multiple controllers side by side, providing a ventilation fan or fans above the controllers will help
maintain a uniform temperature around the controllers.

Keep the front panel of the controller away from the wall (enclosure) by at least 95 mm.

Regardless of whether your system consists of a single controller or multiple controllers, provide sufficient
clearances around each controller so that it can be installed/removed easily.

Fan

50 mm or more

50 mm or more

Airflow

95 mm

or more

[2]

DC solenoid valves, magnet switches and relays

Measure: Install a diode in parallel with the coil. Determine the diode capacity in accordance with the load

capacity.

In a DC circuit, connecting a diode in reverse polarity will damage the
diode, internal parts of the controller and/or DC power supply, so exercise
due caution.