4. W

iring

(2) Wiring the emergency-stop switch

In many cases multiple controllers are used in a single system.
To provide an emergency-stop function for the entire system, the controller circuit is designed in such a way that
a single EMG switch is able to actuate an emergency stop in all connected controllers.

[Internal emergency-stop circuit]

(Note) The current consumption of the internal relay is 10 mA or less.

(Reference)

Cutoff voltage

Cutoff current

EMG switch on teaching pendant

30 VDC

3 A

[Example of recommended circuit]

(Note) To cut off the motor drive power supply in conformance with safety category 2, connect 24V to the EMG

terminal and a contactor or other contact device to the MPI/MPO terminals. (Refer to 4.2.3; rush current:
8 A.)

24V

0V

0V

EMG-

24V

MPO

MPI

S1

S2

0V

Teaching pendant

Relay

Motor power
supply

Input power supply
(2 A max.)

EMG signal

Controller power
supply

PCON-C controller

Connection detection circuit

0V

0V

CR

(3A)

S2

S1

CR

CR

24V

EMG-

24V

MPO

MP1

External EMG
reset switch

External EMG circuit

EMG switch on

teaching pendant

Relay

PCON-C controller

Coil current:

0.1 A or less

Connection detection circuit