3. SCON-CA/CF

A

91

3.5

Setting

Using the teaching tool, set controller parameters. Set the mode toggle switch on the front panel of the

controller to “MANU” side. Refer to the instruction manual for each teaching tool for the applicable version

of the teaching tool that can be applied to EtherNet/IP.

3.5.1

Operation Mode Selecting

Set parameter No. 84 “FMOD: Field bus operation mode.”

[Refer to 3.9 EtherNet/IP Related Parameters.]

Set value

Operation mode

Number of

occupied bytes

0 (Factory setting)

Remote I/O mode

2

1

Position/simplified direct

value mode

8

2

Half direct value mode

16

3

Full direct value mode

32

4

Remote I/O mode 2

12

* Entering any value except for the ones described above will cause an “Excessive Input Value Error”.

3.5.2

Setting the Baud Rate

Set parameter No. 86, “FBRS: Fieldbus baud rate.”

Set value

Baud rate

0 (Factory setting)

Auto negotiation (recommended)

1

10 Mbps, half-duplex

2

10 Mbps, full-duplex

3

100 Mbps, half-duplex

4

100 Mbps, full-duplex

Other than the above

Baud rate setting error

3.5.3

Setting the IP Address

Set parameter No. 140, “IPAD: IP address.”

[Refer to 3.9, “EtherNet/IP Parameters.”]

Settable Range:0.0.0.0 to 255.255.255.255 (It is set to “192.168.0.1” when the machine is delivered from

the factory.)

(Note 1) Exercise caution to avoid IP address duplication.

For details, refer to the operation manuals of the master unit and PLC in which in the master unit

is installed.

(Note 2) When this parameter is set to 0.0.0.0, DHCP (automatic assignment of IP address) is enabled.

Since this setting may result in the IP address being changed unintentionally, it is recommended

that you set the address manually.