beautypg.com

Handling precautions – IAI America PCON-CFA User Manual

Page 16

background image

8

Handling Precautions

1. It is recommended that the baud rate be set based on auto negotiation.

Make sure the link setting of the EtherNet/IP unit matches the communication mode set for the connected

switching hub. If not, the link becomes unstable and communication cannot be performed properly.

It is recommended to enable auto negotiation using an appropriate ACON or PCON parameter.

The table below lists settings for each communication mode of the switching hub:

Fixed to 10 M

Fixed to 100 M

EtherNet/IP unit

Switching hub

Auto negotiation

Full-duplex

Half-duplex

Full-duplex Half-duplex

Auto negotiation

€

(recommended)

X

c

X

c

Full-duplex

X

c

X

X

X

Fixed to 10 M

Half-duplex

c

X

c

X

X

Full-duplex

X

X

X

c

X

Fixed to 100 M

Half-duplex

c

X

X

X

c

(€: Connection possible (recommended), c: Connection possible, X: Connection not possible)

2. Use a switching hub.

Build your network using a switching hub, without using a repeater hub. If a repeater hub is used, tag data

link operation may become unstable. For details, refer to the operation manual for your master unit.

This manual is related to the following products: