(2) I/O signal allocation for each axis

The I/O signals of each axis consist of one input word (16 words = 32 bytes) and one output word in the I/O

areas.

z

Control signals 1 and 2 and status signals are ON/OFF bit signals.

z

The target position and current position are expressed using 2-word (32 bits) binary data. The figures

from –999999 to +999999 (Unit: 0.01mm) can be set in PLC. However, set the position data within the

soft stroke range (0 to effective stroke length) for the actuator concerned.

z

Set the positioning band. The positioning band is expressed using 2-word (32 bits) binary data. The

figures from 1 to +999999 (Unit: 0.01mm) can be set in PLC.

z

The specified speed is expressed using 2-word (32 bits) binary data. The figures from 0 to +999999

(Unit: 0.01mm/sec) can be set in PLC. Set the value that does not exceed the max. speed value for the

actuator concerned.

z

The Acceleration/deceleration is expressed using 1-word (16 bits) binary data. The figures from 1 to 300

(Unit: 0.01G) can be set in PLC. However, set the value that does not exceed the max.

acceleration/deceleration value for the actuator in question.

z

The pressing current-limiting value is expressed using 1-word (16 bits) binary data. The figures from 0

(0%) to 255 (100%) can be set in PLC. However, set the value within the settable range for the pressing

current-limiting value (Refer to the Catalog or operation manual for the actuator) for the actuator

concerned.

Set value

Pressing current-limiting value

z

Set the load current threshold. The load current threshold is expressed using 1-word (16 bits) binary

data. The figures from 0 (0%) to 255 (100%) can be set in PLC. (Refer to the graph of pressing

current-limiting value (above graph).)

z

Zone Boundary “+” and Zone Boundary “–“ are expressed using 2-word (32 bits) binary data. The figures

from -999999 to +999999 can be set in PLC. However make sure to set the smaller value for the Zone

Boundary “-“ than that for the Zone Boundary “+”.

z

The command current is expressed using 2-word (32 bits) binary data (Unit: 1mA).

z

The current speed is expressed using 2-word (32 bits) binary data (Unit: 0.01mm/sec).

z

The alarm code is expressed using 1-word (16 bits) binary data.

z

The total moving count is a 2-word (32-bit) binary data (Unit: times).

z

The total moving distance is a 2-word (32-bit) binary data (Unit: m).