4. SCON-CA

181

(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)

Signal Type

Bit

Symbol

Contents

Details

Current

position

32-bit

-

Current Position: 32-bit signed Integer.

The setting unit is 0.01mm.

(Example)

Reading:000003FF

H

=1023 (decimal)=10.23mm

* When the value is read in hexadecimal notation, the negative figure

is expressed as a complement of 2.

4.8 (1)

Completed

position No.

(Simple

alarm code)

16-bit PM1 to

PM512

16-bit integer

It is moved to the target position and the positioning completed

position No. within the positioning band is output.

In the case that the position movement has not been performed at all,

or during the movement, “0” is output.

When an alarm is issued (in the case that the status signal ALM is

“ON”), the simplified alarm code (Refer to the Operation Manual for

the controller main body) is output.

4.8 (1)

b15

EMGS

Emergency stop: An emergency stop is actuated when this signal

turns ON.

4.6.11 (2)

b14

PWR

Controller ready : This signal turns ON when the controller becomes

ready.

4.6.11 (1)

b13 ZONE2

Zone 2:“ON” for the current position within the zone set range

4.6.11 (12)

b12 ZONE1

Zone 1:“ON” for the current position within the zone set range

4.6.11 (12)

b11 PZONE

Position zone:

This signal turns ON when the current position is inside the specified

position zone.

4.6.11 (12)

b10 MODES

Teaching mode Signal: This signal is ON while the teaching mode is

selected.

4.6.11 (16)

b9

WEND

Position-data read complete : This signal turns ON when reading is

complete.

4.6.11 (17)

b8

RMDS

Operation Mode Status:

This signal is OFF when the current mode is AUTO, or ON when the

current mode is MANU.

4.6.11 (19)

b7

BALM

Absolute battery voltage low warning: This signal turns ON when the

voltage drops.

4.6.11 (28)

b6

-

Unavailable

-

b5

PSEL

Pressing and a Miss: This signal turns ON when the actuator missed

the work part in pressing operation.

4.6.11 (23)

b4

SV

Operation preparation end: This signal turns ON when the servo turns

ON.

4.6.11 (5)

b3

ALM

Alarm: This signal turns ON when an alarm occurs.

4.6.11 (3)

b2

MOVE

Moving Signal: This signal remains ON while the actuator is moving.

4.6.11 (9)

b1

HEND

Home return completion: This signal turns ON when home return is

completed.

4.6.11 (6)

P

LC

in

pu

t

Status code

b0

PEND

Positioning completion signal: This signal turns ON when positioning

is completed.

4.6.11 (10)