IAI America PCON-CFA User Manual

Page 47

background image

2.

ACON-C/CG, PCON-C/CG

39

(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)

Signal type

Bit Symbol

Contents

Details

Current

position

32-bit

data

-

32-bit signed integer indicating the current position

The setting unit is 0.01mm.

(Example) Reading: 000003FF

H

=1023 (decimal)

=10.23mm

* When the value is read in hexadecimal notation, the negative

figure is expressed as

a complement of 2.

2.8 (2)

Command

current

32-bit

data

-

32-bit integer

The electrical current presently specified by a command is indicated.

The setting unit is mA.

(Example) Reading: 000003FF

H

=1023 (decimal)

=1023mA

2.8 (2)

Current

speed

32-bit

data

-

32-bit signed integer indicating the current position

The current speed is indicated.

Positive value: The actuator is moving in the direction opposite

home.

Negative value: The actuator is moving in the direction of home.

The setting unit is 0.01mm/sec.

(Example) Reading: 000003FF

H

=1023 (decimal)

=10.23mm/sec

* When the value is read in hexadecimal notation, the negative

figure is expressed as a complement of 2.

2.8 (2)

Alarm code 16-bit

data

-

16-bit integer

When an alarm is issued, the alarm code is output.

When any alarm is not issued, it is “0

H

”.

Refer to the operation manual for the controller main body for the

details of the alarms.

2.8 (2)

b15 EMGS

Emergency stop: An emergency stop is actuated when this signal

turns ON.

2.6.7 (2)

b14

PWR

Controller ready: This signal turns ON when the controller becomes

ready.

2.6.7 (1)

b13 ZONE2

Zone 2: “ON” for the current position within the zone set range

2.6.7 (12)

b12 ZONE1

Zone 1: “ON” for the current position within the zone set range

2.6.7 (12)

b11
b10

b9

-

Unavailable

-

b8

RMDS

Operation mode status:

This signal is OFF when the current mode is AUTO, or ON when the

current mode is MANU.

2.6.7 (19)

b7
b6

-

Unavailable

-

b5

PSEL

Pressing and a Miss: This signal turns ON when the actuator

missed the work part in pressing operation.

2.6.7 (23)

b4

SV

Operation preparation end: This signal turns ON when the servo

turns ON.

2.6.7 (5)

b3

ALM

Alarm: This signal turns ON when an alarm occurs.

2.6.7 (3)

b2

MOVE

Moving signal: This signal remains ON while the actuator is moving.

2.6.7 (9)

b1

HEND

Home return completion: This signal turns ON when home return is

completed.

2.6.7 (6)

P

LC

in

pu

t

Status

signal

b0

PEND

Positioning completion signal: This signal turns ON when

positioning is completed.

2.6.7 (10)