beautypg.com

IAI America PCON-CFA User Manual

Page 203

background image

4. SCON-CA

195

(3) I/O signal assignment (* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)

Signal type

Bit

Symbol

Contents

Details

Target

position

32-bit

data

-

32-bit signed integer indicating the current position

Set the target position on the absolute coordinates.

The unit is 0.01mm and settable range is–999999 to

+999999.

(Example) When it is “+25.41mm”, set it as “2541”.

If the value larger than the value (0.2mm) inside the soft

limit for the parameter, the movement would be limited to

the inside the soft limit (0.2mm).

* When the input is performed in hexadecimal notation,

input the negative value using a complement of 2.

4.8 (3)

Positioning

band

32-bit

data

-

32-bit integer

The unit is 0.01mm and settable range is 1 to +999999.

(Example) When it is “25.40mm”, set it as “2540”.

This register value has two meanings depending on the

operation type.

1) In the case of positioning operation, it shows the

allowable range from the target position, that is

regarded as the positioning completion.

2) In the case of pressing operation, it shows the

pressing width value. Specify the normal operation or

pressing operation using the “PUSH” control signal

setting.

4.8 (3)

Speed

32-bit

data

-

32-bit integer

Specify the speed at which to move the actuator.

The unit is 0.01 mm/sec and the settable range is 0 to

999999.

(Example) When it is “25.41mm/sec”, set it as “2541”.

When the movement command is set with the value

bigger than the max. speed, an alarm is issued.

4.8 (3)

P

LC

o

ut

pu

t

Zone

boundary+/

Zone

boundary–

32-bit

data

-

32-bit signed integer indicating the current position

After completion of home return, an effective zone signal

can be output separately from the zone boundaries

specified by parameters.

The status signal PZONE turns ON when the current

position is inside these +/- boundaries. (Example) When

it is “+25.40mm”, set it as “2540”.

The unit is 0.01mm and the settable range is -999999 to

999999.

Enter a value that satisfies the relationship of “Zone

boundary + > Zone boundary –”.

If this function is not used, enter the same value for both

the positive and negative boundaries.

* When the input is performed in hexadecimal notation,

input the negative value using a complement of 2.

4.8 (3)

This manual is related to the following products: