4. SCON-CA

208

(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)

Signal type

Bit

Symbol

Contents

Details

Current

position

32-bit

-

Current Position: 32-bit signed Integer.

The setting unit is 0.01mm.

(Example)

Reading:000003FF

H

=1023 (decimal)=10.23mm

* When the value is read in hexadecimal notation, the

negative figure is expressed as a complement of 2.

4.8 (1)

Completed

position

number

(Simple alarm

code)

16-bit

PM1 to

PM512

16-bit integer

It is moved to the target position and the positioning completed

position No. within the positioning band is output.

In the case that the position movement has not been

performed at all, or during the movement, “0” is output.

When an alarm is issued (in the case that the status signal

ALM is “ON”), the simplified alarm code (Refer to the

Operation Manual for the controller main body) is output.

4.8 (1)

b15

EMGS Emergency stop: An emergency stop is actuated when this

signal turns ON.

4.6.11 (2)

b14

PWR Controller ready : This signal turns ON when the controller

becomes ready.

4.6.11 (1)

b13

CEND Load cell calibration complete: This signal turns ON when the

load cell calibration is complete.

4.6.11 (32)

b12

ZONE1 Zone 1:“ON” for the current position within the zone set range 4.6.11 (12)

b11

PZONE/

ZONE2

PZONE and ZONE2 can be switched in Parameter No.149.

No.149 = 0 : This signal turns ON when the current

Position zone position is inside the specified position zone.

No.149 = 1 : This signal turns ON when the

Zone2

current position is inside the specified zone.

4.6.11 (12)

b10

LOAD

Load output judgment:

When this signal is ON, the specified load output judgment

has been reached. If the signal is OFF, it is not yet reached.

(For details, refer to the operation manual for your controller.)

4.6.11 (26)

b9

TRQS

Torque level:

When this signal is ON, the specified torque level has been

reached. If the signal is OFF, it is not yet reached.

(For details, refer to the operation manual for your controller.)

4.6.11 (27)

b8

RMDS

Operation Mode Status:

This signal is OFF when the current mode is AUTO, or ON

when the current mode is MANU.

4.6.11 (19)

b7

BALM Absolute battery voltage low warning: This signal turns ON

when the voltage drops.

4.6.11 (28)

b6

PUSHS Pressing operation in progress: The signal is ON when the

Pressing operation in progress.

4.6.11 (25)

b5

PSFL Pressing and a Miss: This signal turns ON when the actuator

missed the work part in pressing operation.

4.6.11 (23)

b4

SV

Operation preparation end: This signal turns ON when the

servo turns ON.

4.6.11 (5)

b3

ALM Alarm: This signal turns ON when an alarm occurs.

4.6.11 (3)

b2

MOVE Moving Signal: This signal remains ON while the actuator is

moving.

4.6.11 (9)

b1

HEND Home return completion: This signal turns ON when home

return is completed.

4.6.11 (6)

PLC

input

Status code

b0

PEND Positioning completion signal: This signal turns ON when

positioning is completed.

4.6.11 (10)