IAI America PCON-CFA User Manual

Page 56

background image

2.

ACON-C/CG, PCON-C/CG

48

(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)

Signal type

Bit

Symbol

Contents

Details

Current

position

32-bit

data

-

32-bit signed integer indicating the current position

The setting unit is 0.01mm.

(Example) Reading:000003FF

H

=1023 (decimal)

=10.23mm

* When the value is read in hexadecimal notation, the negative figure is

expressed as a complement of 2.

2.8 (3)

Command

current

32-bit

data

-

32-bit integer

The electrical current presently specified by a command is indicated.

The setting unit is mA.

(Example) Reading:000003FF

H

=1023 (decimal)

=1023mA

2.8 (3)

Current

speed

32-bit

data

-

32-bit signed integer indicating the current position

The current speed is indicated.

Positive value: The actuator is moving in the direction opposite home.

Negative value: The actuator is moving in the direction of home.

The setting unit is 0.01mm/sec.

(Example) Reading:000003FF

H

=1023 (decimal)

=10.23mm/sec

* When the value is read in hexadecimal notation, the negative figure is

expressed as a complement of 2.

2.8 (3)

Alarm

code

16-bit

data

-

16-bit integer

When an alarm is issued, the alarm code is output.

When any alarm is not issued, it is “0”.

Refer to the operation manual for the controller main body for the details of the

alarms.

2.8 (3)

b15

EMGS

Emergency stop: An emergency stop is actuated when this signal turns ON.

2.6.7 (2)

b14

PWR

Controller ready : This signal turns ON when the controller becomes ready.

2.6.7 (1)

b13

ZONE2

Zone 2:“ON” for the current position within the zone set range

2.6.7 (12)

b12

ZONE1

Zone 1:“ON” for the current position within the zone set range

2.6.7 (12)

b11

PZONE

Position zone:

This signal turns ON when the current position is inside the specified position

zone.

2.6.7 (12)

ACON - Unavailable (ON/OFF is undefined)

-

b10 PCON LOAD

Load output judgment:

When this signal is ON, the specified load has been reached. When the signal

is OFF, the load has not been reached yet.

(Refer to operation manual for the controller main body for more information)

2.6.7 (26)

ACON - Unavailable (ON/OFF is undefined)

-

b9

PCON TROS

Torque level:

When this signal is ON, the specified load has been reached. When the signal

is OFF, the load has not been reached yet.

(Refer to operation manual for the controller main body for more information)

2.6.7 (27)

b8

RMDS

Operation mode status:

This signal is OFF when the current mode is AUTO, or ON when the current

mode is MANU.

2.6.7 (19)

b7

GHMS

Under Home return Operation: This signal remains ON while home return is in

progress.

2.6.7 (6)

b6

PUSHS Pressing in progress: This signal remains ON while pressing operation is in

progress.

2.6.7 (25)

b5

PSEL

Pressing and a Miss: This signal turns ON when the actuator missed the work

part in pressing operation.

2.6.7 (23)

b4

SV

Operation preparation end: This signal turns ON when the servo turns ON.

2.6.7 (5)

b3

ALM

Alarm: This signal turns ON when an alarm occurs.

2.6.7 (3)

b2

MOVE

Moving signal: This signal remains ON while the actuator is moving.

2.6.7 (9)

b1

HEND

Home return completion: This signal turns ON when home return is completed.

2.6.7 (6)

PL

C

in

pu

t

Status

signal

b0

PEND

Positioning completion signal: This signal turns ON when positioning is

completed.

2.6.7 (10)