beautypg.com

IAI America PCON-CFA User Manual

Page 65

background image

2.

ACON-C/CG, PCON-C/CG

57

Travel

Speed

Positioning band

Time

Target position

Timing at which the position

complete signal turns ON

(10) Positioning completion signal (PEND) PLC input signal

This signal is turned “ON” when the actuator is moved to the target position and reaches the positioning

band and the pressing is completed.

When the servo-motor is turned ON from OFF condition, the positioning is performed with the position set

as the target position. Accordingly, this signal is turned “ON” and after that, when the positioning operation

is started with the home return (HOME) signal, positioning start (CSTR) signal and positioning command

(DSTR) signal, this signal is turned “OFF”.

Caution: When the servo-motor is turned OFF or stopped in an emergency while the actuator is

stopped at the target position, the PEND signal is turned “OFF” temporarily.

Then, when the servo-motor is turned “ON” and the actuator is within the positioning band, the

PEND signal is turned “ON” again.

When the positioning is completed with the CSTR signal or DSTR signal turned “ON”, the

PEND signal is not turned “ON”.

(11) Pause (STP) PLC output signal

When this signal is turned “ON”, the actuator movement is decelerated and stopped. When it is turned

“OFF”, the actuator movement is restarted.

The acceleration in the operation restart or the deceleration in stopping operation, is expressed as the value

for the acceleration/deceleration for the position No. set using the specified position No. resister in the

Position/Simplified Direct Value Mode, and as the value set in the acceleration/deceleration register in the

Half direct value mode.

In the Full direct value mode, the value is expressed as the value set in the acceleration register or

deceleration register.

This manual is related to the following products: