3. SCON-CA/CF

A

118

(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)

Address

Bit

Symbol

Function

Details

Acceleration

16-bit

data

-

Deceleration

16-bit

data

-

16-bit integer

Specify the acceleration and deceleration at which to move

the actuator.

The unit is 0.01G and settable range is 1 to 300.

(Example) When it is “0.30G”, set it as “30”.

If a move command is issued by specifying “0” or any value

exceeding the maximum acceleration or deceleration, an

alarm will occur.

3.8 (3)

Pressing

current-limiting

value

16-bit

data

-

16-bit integer

Specify the current- limiting value to be used during pressing

operation. The allowable specification range is 0 (0%) to 255

(100%).

The actual settable range varies depending on each actuator.

(Refer to the catalog or operation manual for the actuator.)

If a move command is issued by specifying a value exceeding

the maximum pressing current, an alarm will occur.

3.8 (3)

Load current

threshold

16-bit

data

-

16-bit integer

Set the current threshold in this register when whether or not

the load current exceeds the threshold is judged.

The allowable specification range is 0 (0%) to 255 (100%). If

threshold judgment is not required, enter “0”.

3.8 (3)

b15
b14
b13
b12
b11

-

Unavailable

-

b10

SMOD

Stopping control mode: When this signal is ON, servo control

is performed during stopping.

3.6.7

(28)

b9

ASO1

Stop

Mode 1

b8

ASO0

Stop

Mode 0

Select stop mode while standing by

ASO1

ASO0

Functions

OFF

OFF

Disable

(Servo is ON at all times)

OFF

ON

Sever turns OFF in time set

in Parameter No. 36

ON

OFF

Sever turns OFF in time set

in Parameter No. 37

ON

ON

Sever turns OFF in time set

in Parameter No. 38

3.6.7

(30)

b7

MOD1

b6

MOD0

Acceleration / deceleration mode:

When both signals are OFF, the trapezoid pattern mode is

selected.

When one signal is OFF and the other signal is ON, the

S-motion mode is selected. When one signal is ON and the

other signal is OFF, the primary delay filter mode is selected.

3.6.7

(29)

b5

b4

-

Unavailable

-

PLC

output

Control

signal 1

b3

INC

Incremental Command:

Absolute position commands are issued when this signal is

OFF, and incremental position commands are issued when

the signal is ON.

3.6.7

(24)