Mitsubishi FX3U PLC
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: D0 / D10.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type
Format
Word No.
Bit No.
Data length
Auxiliary Relay
Mn
n: 0 ~ 7679
N/A
Word
Special Auxiliary Relay
Mn
n: 8000 ~ 8511
N/A
Word
Status Relay
Sn
n: 0 ~ 4095
N/A
Word
Input Relay
Xn
n: 0 ~ 377(octal)
N/A
Word
Output Relay
Yn
n: 0 ~ 377(octal)
N/A
Word
Timer PV
Tn
n: 0 ~ 255
N/A
Word
16-bit Counter PV
Cn
n: 0 ~ 199
N/A
Word
32-bit Counter PV
Cn
n: 200 ~ 255
N/A
Double Word
Data Register
Dn
n: 0 ~ 7999
N/A
Word
Special Data Register
Dn
n: 8000 ~ 8511
N/A
Word
¾
Auxiliary Relay/ Special Auxiliary Relay/ Status Relay/ Input Relay /Output Relay: Address must be the
multiple of 16.
Contacts
Read/Write Range
Contact type
Format
Word No.
Bit No.
Auxiliary Relay
Mn
N/A
n: 0 ~ 7679
Special Auxiliary Relay
Mn
N/A
n: 8000 ~ 8511
Status Relay
Sn
N/A
n: 0 ~ 4095
Input Relay
Xn
N/A
n: 0 ~ 377(octal)
Output Relay
Yn
N/A
n: 0 ~ 377(octal)
Timer Flag
Tn
N/A
n: 0 ~ 255
Counter Flag
Cn
N/A
n: 0 ~ 255