Mitsubishi FX3U PLC

Back to Table

A. HMI factory settings

Baud rate: 9600, 7, EVEN, 1.

Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)

communication is allowed.)

Control area/status area: D0 / D10.

B. Definition of controller Read/Write address

Registers

Read/Write Range

Register Type

Format

Word No.

Bit No.

Data length

Auxiliary Relay

Mn

n: 0 ~ 7679

N/A

Word

Special Auxiliary Relay

Mn

n: 8000 ~ 8511

N/A

Word

Status Relay

Sn

n: 0 ~ 4095

N/A

Word

Input Relay

Xn

n: 0 ~ 377(octal)

N/A

Word

Output Relay

Yn

n: 0 ~ 377(octal)

N/A

Word

Timer PV

Tn

n: 0 ~ 255

N/A

Word

16-bit Counter PV

Cn

n: 0 ~ 199

N/A

Word

32-bit Counter PV

Cn

n: 200 ~ 255

N/A

Double Word

Data Register

Dn

n: 0 ~ 7999

N/A

Word

Special Data Register

Dn

n: 8000 ~ 8511

N/A

Word

¾

Auxiliary Relay/ Special Auxiliary Relay/ Status Relay/ Input Relay /Output Relay: Address must be the

multiple of 16.

Contacts

Read/Write Range

Contact type

Format

Word No.

Bit No.

Auxiliary Relay

Mn

N/A

n: 0 ~ 7679

Special Auxiliary Relay

Mn

N/A

n: 8000 ~ 8511

Status Relay

Sn

N/A

n: 0 ~ 4095

Input Relay

Xn

N/A

n: 0 ~ 377(octal)

Output Relay

Yn

N/A

n: 0 ~ 377(octal)

Timer Flag

Tn

N/A

n: 0 ~ 255

Counter Flag

Cn

N/A

n: 0 ~ 255