Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

1-34

Revision January, 2008, Doc. Name: 2007PDD23000007

GE Fanuc 90 Series SNP PLC

Back to Table

A. HMI factory settings

Baud rate: 19200, 8, ODD, 1.

Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)

communication is allowed.)

Control area/status area: %R1 / %R10.

NOTE

1) Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication

is allowed.

2) If the PLC enabled “Check Password” function, the user needs to set the password by clicking Option >

Configuration > Communication. The user can find Controller Settings and set PLC password on

Communication Tab in the Configuration dialog box. Please enter a 4-digit password (If entering a

password that exceeds 4-digit number, only the first 4-digit number is valid).

B. Definition of controller Read/Write address

Registers

Read/Write range

Register Type

Format

Word No.

Bit No.

Data length

Discrete Inputs

%In

n: 1 ~ 12288

N/A

Word (the multiple of 16 + 1)

Discrete Outputs

%Qn

n: 1 ~ 12288

N/A

Word (the multiple of 16 + 1)

Discrete Temporaries

%Tn

n: 1 ~ 256

N/A

Word (the multiple of 16 + 1)

Discrete Internals

%Mn

n: 1 ~ 12288

N/A

Word (the multiple of 16 + 1)

%SA Discretes

%SAn

n: 1 ~ 128

N/A

Word (the multiple of 16 + 1)

%SB Discretes

%SBn

n: 1 ~ 128

N/A

Word (the multiple of 16 + 1)

%SC Discretes

%SCn

n: 1 ~ 128

N/A

Word (the multiple of 16 + 1)

%S Discretes

%S-n

n: 1 ~ 128

N/A

Word (the multiple of 16 + 1)

Genius Global Data

%Gn

n: 1 ~ 7680

N/A

Word (the multiple of 16 + 1)

Registers

%Rn

n: 1 ~ 16384

N/A

Word

Analog Inputs

%AIn

n: 1 ~ 8192

N/A

Word

Analog Outputs

%AQn

n: 1 ~ 8192

N/A

Word