GE Fanuc 90 Series SNP PLC
A. HMI factory settings
Baud rate: 19200, 8, ODD, 1.
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: %R1 / %R10.
NOTE
1) Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication
is allowed.
2) If the PLC enabled “Check Password” function, the user needs to set the password by clicking Option >
Configuration > Communication. The user can find Controller Settings and set PLC password on
Communication Tab in the Configuration dialog box. Please enter a 4-digit password (If entering a
password that exceeds 4-digit number, only the first 4-digit number is valid).
B. Definition of controller Read/Write address
Registers
Read/Write range
Register Type
Format
Word No.
Bit No.
Data length
Discrete Inputs
%In
n: 1 ~ 12288
N/A
Word (the multiple of 16 + 1)
Discrete Outputs
%Qn
n: 1 ~ 12288
N/A
Word (the multiple of 16 + 1)
Discrete Temporaries
%Tn
n: 1 ~ 256
N/A
Word (the multiple of 16 + 1)
Discrete Internals
%Mn
n: 1 ~ 12288
N/A
Word (the multiple of 16 + 1)
%SA Discretes
%SAn
n: 1 ~ 128
N/A
Word (the multiple of 16 + 1)
%SB Discretes
%SBn
n: 1 ~ 128
N/A
Word (the multiple of 16 + 1)
%SC Discretes
%SCn
n: 1 ~ 128
N/A
Word (the multiple of 16 + 1)
%S Discretes
%S-n
n: 1 ~ 128
N/A
Word (the multiple of 16 + 1)
Genius Global Data
%Gn
n: 1 ~ 7680
N/A
Word (the multiple of 16 + 1)
Registers
%Rn
n: 1 ~ 16384
N/A
Word
Analog Inputs
%AIn
n: 1 ~ 8192
N/A
Word
Analog Outputs
%AQn
n: 1 ~ 8192
N/A
Word