Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
Revision January, 2008, Doc. Name: 2007PDD23000007
1-59
LG Glofa GM6 CNET
A. HMI factory settings
Baud rate: 19200, 8, None, 1. (RS-232)
Controller station number: 0.
Control area/status area: %MW0 / %MW10.
NOTE
1) HMI default setting is predefined for CPU Port. If the user want to connect to CNET communication
module, the baud rate should be changed to 38400, 8, None, 1. (RS-422 / RS-485).
B. Definition of controller Read/Write address
Registers
Register Type
Format
Word No.
Bit No.
Data Size
Input Image
IWb.s.w
w(word):0 ~ 3
s(slot): 0 ~ 7
b(base): 0 ~ 1
Word
Input Image
IDb.s.w
w(word):0 ~ 1
s(slot): 0 ~ 7
b(base): 0 ~ 1
DWord
Output Image
QWb.s.w
w(word):0 ~ 3
s(slot): 0 ~ 7
b(base): 0 ~ 1
Word
Output Image
QDb.s.w
w(word):0 ~ 1
s(slot): 0 ~ 7
b(base): 0 ~ 1
DWord
Internal Memory
MWn
n: 0 ~ 4095
N/A
Word
Internal Memory
MDn
n: 0 ~ 2047
N/A
DWord
Contacts
Contact type
Format
Word No.
Bit No.
Input Image
IXb.s.n
s(slot): 0 ~ 7
n(bit): 0 ~ 63
b(base): 0 ~ 1
Output Image
QXb.s.n
s(slot): 0 ~ 7
n(bit): 0 ~ 63
b(base): 0 ~ 1
Internal Memory
MXn
N/A
n: 0 ~ 65535