Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

1-14

Revision January, 2008, Doc. Name: 2007PDD23000007

AllenBradley MicroLogix PLC

Back to Table

A. HMI factory setting

Baud rate: 19200, 8, None, 1.

PLC station number: 1.

Control area/status area: B3:0/B3:10.

B. Definition of controller Read/Write address

Registers

Read/Write Range

Bit No.

Register Type

Format

Word No.

Low Byte

High Byte

File No.

Output File

O:n

n: 0 ~ 3

N/A

0

Input File

I:n

n: 0 ~ 3

N/A

1

Status File

S2:n

n: 0 ~ 65

N/A

2

Bit File

B3:n

n: 0 ~ 255

N/A

3

Timer Flag

T4:n

n: 0 ~ 255

N/A

4

Timer Preset Value

T4:n.PRE

n: 0 ~ 255

N/A

4

Timer Accumulator Value

T4:n.ACC

n: 0 ~ 255

N/A

4

Counter Flag

C5:n

n: 0 ~ 255

N/A

5

Counter Preset Value

C5:n.PRE

n: 0 ~ 255

N/A

5

Counter Accumulator Value

C5:n.ACC

n: 0 ~ 255

N/A

5

Control File

R6:n

n: 0 ~ 255

N/A

6

Control Size of Bit Array

R6:n.LEN

n: 0 ~ 255

N/A

6

Control Reserved File

R6:n.POS

n: 0 ~ 255

N/A

6

Integer File

N7:n

n: 0 ~ 255

N/A

7

¾

Bit No : Low byte is not used, so the value is 0. High byte stores file number.

¾

Data Size : Word.

¾

T4, C5 and R6 only read 1 Word once.

¾

If reading multiple Words once, the communication speed of PLC will be slow.

NOTE

1) After last communication data has been memorized by PLC (PLC will send 0x10 0x05 consecutively),

communication may fail. At this time, power off and power up HMI or power off and power up PLC once.