beautypg.com

Delta Electronics Network Device DOP-A/AE/AS User Manual

Page 56

background image

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Revision January, 2008, Doc. Name: 2007PDD23000007

1-55

y

00 indicates the global broadcasting number (1~99).

y

10, 20, 30, 40, 50, 60, 70, 80, 90 are local broadcasting number.

The affected ranges are: 11~19, 21~29, 31~39, 41~49, 51~59, 61~69, 71~79, 81~89 and 91~99

respectively. Only choose setting value/setting constant (button), and then the broadcast function

can be used. If choosing other devices, the system will be confused while reading back the drive

setting value via broadcast function, so please ensure to choose the correct device. If choosing the

incorrect devices, a “Controller Station Number Error…” fault message will display on HMI screen.

y

Use in LECOM-A/B protocol. 82XX frequency AC drives and 93XX servo drives all use this protocol.

4) Explanation of communication error address

y

Registers: display CW n, CWy n, CD n, CDy n in order

y

Contacts: display CB n, CByn in order (n: address value)

5) HMI data format explanation

y

Some controller parameters are in Word and some are in Double Word. Therefore, there are two

kinds of data format: Word ( CWn (CWn.m), CWn/y(CWn/y.m) ) and Double Word ( CDn (CDn.m),

CDn/y(CDn/y.m) ).

y

Furthermore, regarding to Bit No., HMI only read/write 32Bit (Bit0 ~ Bit31) of parameters in VH

format.

y

CWn(CWn.m), CDn(CDn.m), or CBn.b: read/write address is the same (address n), but

When symbol is set to CW, read/write value is the low word of parameters (n) only,

When symbol is set to CD, read/write value is the Double Word of whole parameters (n),

When symbol is set to CB, read/write value is the Bit (b) No. of parameters (n).

(m : HMI communication data format)

y

(CWn/y(CWn/y.m), CDn/y(CDn/y.m), CBn/y.b: read/write address, which y subcode is the

same(address n), but

When symbol is set to CW, read/write value is the low word of parameters (n) only,

When symbol is set to CD, read/write value is the Double Word of whole parameters (n),

When symbol is set to CB, read/write value is the Bit (b) No. of parameters (n).

(m : HMI communication data format)

y

Actually when using HMI,

i)

When using devices that the unit is in Word (e.g. numeric devices (numeric value display,

numeric value input…)…), the read/write value will be the same no matter the read/write

address format is set to CWn or CDn as read/write value is the low word of parameters (n)

only.

ii)

When using devices that the unit is in Double Word (e.g. numeric devices (numeric value

display, numeric value input…)…), if the read/write address format is set to CWn,

read/write value is coming from the low word of CWn and CWn+1 these two addresses.

(The low word of CWn is regarded as “low word” and the low word of CWn+1 is regarded

as “high word”, and then combining “low word” and “high word” to a Double Word.)