Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Revision January, 2008, Doc. Name: 2007PDD23000007

1-17

AllenBradley SLC5 PLC

Back to Table

A. HMI factory setting

Baud rate: 19200, 8, None, 1.

PLC station number: 1.

Control area/status area: B3:0/B3:10.

NOTE

1) Error Check uses CRC (Cyclical Redundancy Check).

B. Definition of controller Read/Write address

Registers

Read/Write Range

Word No.

Bit No.

Low Byte

High Byte

Register Type

Format

Element No.

Slot or File No.

Output File

O:n
O:s.n

n: 0 ~ 30

N/A

Slot No. s = 0
s: 0 ~ 255
File No. = 0

Input File

I:n
I:s.n

n: 0 ~ 30

N/A

Slot No. s = 0
s: 0 ~ 255
File No. = 1

Status File

S2:n

n: 0 ~ 255

N/A

File No. = 2

Bit File

Bf:n

n: 0 ~ 255

N/A

f: 10 ~ 255
If f is ignored, file no. will be
default setting 3.

Timer Flag

Tf:n

n: 0 ~ 255

N/A

f: 10 ~ 255
If f is ignored, file no. will be
default setting 4.

Timer Preset Value

Tf:n.PRE

n: 0 ~ 255

N/A

f: 10 ~ 255
If f is ignored, file no. will be
default setting 4.

Timer Accumulator Value

Tf:n.ACC

n: 0 ~ 255

N/A

f: 10 ~ 255
If f is ignored, file no. will be
default setting 4.

Counter Flag

Cf:n

n: 0 ~ 255

N/A

f: 10 ~ 255
If f is ignored, file no. will be
default setting 5.

Counter Preset Value

Cf:n.PRE

n: 0 ~ 255

N/A

f: 10 ~ 255
If f is ignored, file no. will be
default setting 5.