Delta Electronics Network Device DOP-A/AE/AS User Manual
Page 46
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
Revision January, 2008, Doc. Name: 2007PDD23000007
1-45
NOTE
When using the protocol format of KV series and connecting to KZ-80T PLC, some errors occur. Please refer
to the following description:
1) Readable Timer address is not continuous. For example, T-0 ~ T-9 can be read, T10 cannot be read,
T11 ~ T20 can be read, T21 ~ T50 cannot be read, …etc.
2) Counter cannot be read. For example,
Registers: C- (Counter), CTH- (High-speed counter), CTC- (High-speed counter comparator),
PC- (Counter preset value), PCTC- (CTC preset value) they all cannot be read.
Contacts: C- (Counter), CTC- (High-speed counter comparator) they all cannot be read also.
C. Connections (Connector Pinouts)
RS-232
KV Series
DOP
9 pin D-SUB male (RS-232)
Controller
RJ-11 cable connector (RS-232)
Controller
RJ-11 cable connector (RS-232)
RXD (2)
(3) SD
TXD (3)
GND (5)
(5) RD
(4) SG
Top View
6 - 1
PLC side (Comm. Port)
KZ Series
DOP
9 pin D-SUB male (RS-232)
Controller
RJ-11 cable connector (RS-232)
Controller
RJ-11 cable connector (RS-232)
RXD (2)
(5) SD
TXD (3)
GND (5)
(3) RD
(4) SG
Top View
6 - 1
PLC side (Comm. Port)