Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
Revision January, 2008, Doc. Name: 2007PDD23000007
1-69
Matsushita FP PLC
A. HMI factory settings
Baud rate: 9600, 8, ODD, 1.
Controller station number: 238.
Control area/status area: DT0 / DT10.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type
Format
Word No.
Bit No.
Data length
Internal Relay
WRn
n: 0 ~ 886,
N/A
Word
Special Internal Relay
900 ~ 910
Link Relay
WLn
n: 0 ~ 639
N/A
Word
External Input Relay
WXn
n: 0 ~ 511
N/A
Word
External Output Relay
WYn
n: 0 ~ 511
N/A
Word
Timer/Counter P.V.
EVn
n: 0 ~ 3071
N/A
Word
Timer/Counter S.V.
SVn
n: 0 ~ 3071
N/A
Word
Data Register
DTn
n: 0 ~ 32764
N/A
Word
Link Data Register
LDn
n: 0 ~ 8447
N/A
Word
File Register
FLn
n: 0 ~ 32764
N/A
Word
Special Data Register
DT9_n
n: 0 ~ 511
N/A
Word
¾
DT9_0 ~ DT9_511 are applicable for FP0 T32C, FP2, FP2SH, FP10SH controllers. (Special data
registers are all within the range of DT90000 ~ DT9XXXX).
¾
The actual transmitted address of DT9_n is 90000 + n (for DT). For example, the actual transmitted
address of DT9_1 is 90001 (for DT), the actual transmitted address of DT9_2 is 90002 (for DT) and vise
versa.
Contacts
Read/Write Range
Contact type
Format
Word No.
Bit No.
Internal Relay
Rnb
n: 0 ~ 886
b: 0 ~ f
Special Internal Relay
n: 900 ~ 910
b: 0 ~ f
Link Relay
Lnb
n: 0 ~ 639
b: 0 ~ f
External Input Relay
Xnb
n: 0 ~ 511
b: 0 ~ f
External Output Relay
Ynb
n: 0 ~ 511
b: 0 ~ f
Timer Flag Contact
Tn
N/A
n: 0 ~ 3071
Counter Flag Contact
Cn
N/A
n: 0 ~ 3071