Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Revision January, 2008, Doc. Name: 2007PDD23000007

1-69

Matsushita FP PLC

Back to Table

A. HMI factory settings

Baud rate: 9600, 8, ODD, 1.

Controller station number: 238.

Control area/status area: DT0 / DT10.

B. Definition of controller Read/Write address

Registers

Read/Write Range

Register Type

Format

Word No.

Bit No.

Data length

Internal Relay

WRn

n: 0 ~ 886,

N/A

Word

Special Internal Relay

900 ~ 910

Link Relay

WLn

n: 0 ~ 639

N/A

Word

External Input Relay

WXn

n: 0 ~ 511

N/A

Word

External Output Relay

WYn

n: 0 ~ 511

N/A

Word

Timer/Counter P.V.

EVn

n: 0 ~ 3071

N/A

Word

Timer/Counter S.V.

SVn

n: 0 ~ 3071

N/A

Word

Data Register

DTn

n: 0 ~ 32764

N/A

Word

Link Data Register

LDn

n: 0 ~ 8447

N/A

Word

File Register

FLn

n: 0 ~ 32764

N/A

Word

Special Data Register

DT9_n

n: 0 ~ 511

N/A

Word

¾

DT9_0 ~ DT9_511 are applicable for FP0 T32C, FP2, FP2SH, FP10SH controllers. (Special data

registers are all within the range of DT90000 ~ DT9XXXX).

¾

The actual transmitted address of DT9_n is 90000 + n (for DT). For example, the actual transmitted

address of DT9_1 is 90001 (for DT), the actual transmitted address of DT9_2 is 90002 (for DT) and vise

versa.

Contacts

Read/Write Range

Contact type

Format

Word No.

Bit No.

Internal Relay

Rnb

n: 0 ~ 886

b: 0 ~ f

Special Internal Relay

n: 900 ~ 910

b: 0 ~ f

Link Relay

Lnb

n: 0 ~ 639

b: 0 ~ f

External Input Relay

Xnb

n: 0 ~ 511

b: 0 ~ f

External Output Relay

Ynb

n: 0 ~ 511

b: 0 ~ f

Timer Flag Contact

Tn

N/A

n: 0 ~ 3071

Counter Flag Contact

Cn

N/A

n: 0 ~ 3071