beautypg.com

Delta Electronics Network Device DOP-A/AE/AS User Manual

Page 104

background image

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Revision January, 2008, Doc. Name: 2007PDD23000007

1-103

CrossReference Table (Inter Memoryof Delta HMI and Modbus Reference Address)

Inter Memory

of Delta HMI

Modbus Reference

Address

Supporting Modbus

Function

Address of Function

$0 40001 03H,

06H,

10H

0000H

$1 40002 03H,

06H,

10H

0001H

.
.
.

$1023 41024

03H,

06H,

10H

03FFH

$M0 42001 03H,

06H,

10H

07D0H

$M1 42002 03H,

06H,

10H

07D1H

.
.
.

$M1023 43024

03H,

06H,

10H 0BCFH

RCPNO 44001

03H,

06H

0FA0H

RCP0 45001

03H,

06H,

10H

1388H

RCP1 45002

03H,

06H,

10H

1389H

.
.
.

$2000.0 00001

01H,

05H,

0FH 0000H

$2000.1 00002

01H,

05H,

0FH 0001H

.
.
.

$2000.15 00016

01H,

05H,

0FH 000FH

$2001.0 00017

01H,

05H,

0FH 0010H

.
.
.

$2063.0 01009

01H,

05H,

0FH 03F0H

.
.
.

$2063.15 01024

01H,

05H,

0FH 03FFH

$M200.0 01025

01H,

05H,

0FH 0400H