Logic connections, Operational settings – Basler Electric BE1-11g User Manual
Page 94

82
9424200994 Rev N
Logic Connections
Frequency element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The
frequency element logic block is illustrated in Figure 54. Logic inputs and outputs are summarized in
Table 26.
Figure 54. Frequency Element Logic Block
Table 26. Logic Inputs and Outputs
Name
Logic Function
Purpose
Block
Input
Disables the 81 function when true
Trip
Output
True when the 81 element is in a trip condition
Pickup
Output
True when the 81 element is in a pickup condition
Operational Settings
Frequency element operational settings are configured on the Frequency settings screen (Figure 55) in
BESTCOMSPlus. Setting ranges and defaults are summarized in Table 27.
Figure 55. Frequency Settings Screen
Table 27. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
Disabled, Over, Under,
Rate of Change,
Positive Rate of Change,
or Negative Rate of Change
n/a
n/a
Disabled
Source
Phase VT or Aux VT
n/a
n/a
Phase VT
Pickup
0 or 0.2 to 20 for ROC mode
0 or 15 to 70 for O/U mode
0.01
hertz/sec (ROC)
hertz (O/U)
0
Time Delay
0 to 600,000
varies
milliseconds
0
Frequency (81) Protection
BE1-11g