Block V2 Voltage Elements

All functions that use the negative-sequence voltage (V2)
measurement are blocked when the 60FL logic is true. (27X, 59X -
V2 mode)

Block Power/Power Factor
Elements

All functions that use the power measurements are blocked when
the 60FL logic is true. (32)

Block Impedance Elements

All functions that use the impedance measurement are blocked
when the 60FL logic is true. (21 and 40Z)

Ignore Breaker Status

When enabled, breaker status is ignored.

Fuse Loss (60FL)

BE1-11g