Terminals and connectors, J type case, Be1-11 g terminals and connectors – Basler Electric BE1-11g User Manual
Page 277

9424200994 Rev N
265
Terminals and Connectors
Connections to the BE1-11g are dependent on the application and logic scheme selected by the user. As
a result, some BE1-11g inputs and outputs may not be used for a given application. Before energizing a
BE1-11g, make sure the connections match the options associated with the model and style number
found on the BE1-11g nameplate. Refer to the style chart in the
chapter for available options.
Be sure to use the correct input power for the specified power supply. Incorrect wiring may result in
damage to the BE1-11g.
Note
Connections to the BE1-11g voltage inputs, contact inputs, power
supply inputs, and contact outputs should be made with a minimum
wire size of 14 AWG (2.08 mm
2
).
Connections to the BE1-11g current inputs and ground terminal should
be made with a minimum wire size of 12 AWG (3.31 mm
2
).
When the BE1-11g is configured in a system with other protective
devices, a separate ground bus lead is recommended for each BE1-
11g.
BE1-11g protection systems are supplied in either an S1 size case (J option) or an H1 size case (H or P
option).
J Type Case
Figure 199 shows the rear-panel connections with an RJ45 Ethernet connector. Figure 200 shows the
rear-panel connections with a fiber optic Ethernet connector.
Figure 199. Rear-Panel Connections with RJ45 Ethernet (J Type Case)
ETHERNET
!
WARNING
BE1-11
C12
C11
C10
C9
C8
C7
C6
C5
C4
C3
C2
C1
C13
C14
C15
C16
C17
C18
V
A
OUT 2
OUT 3
OUT 4
OUT 5
OUT 1
ALARM
V
B
V
C
V
X
V
X
N
E12
E11
E10
E9
E8
E7
E6
E5
E4
E3
E2
E1
OUT 8
OUT 7
IN5
IN6
IN7
OUT 6
A8
A7
A6
A5
A4
A3
A2
A1
IRIG
PWR
C
A
B
RS-485
GND
B8
B7
B6
B5
B4
B3
B2
B1
IN1
IN2
IN3
IN4
D1
D3
D5
D7
IA1
IB1
IC1
IG1
IA1
D2
D4
D6
D8
IB1
IC1
IG1
IA2
F2
F4
F6
F8
IB2
IC2
IG2
F1
F3
F5
F7
IA2
IB2
IC2
IG2
P0061-43
BE1-11g
Terminals and Connectors