Functional test report - pll – Basler Electric BE1-11g User Manual
Page 530
518
9424200994 Rev N
Figure 316. BESTlogicPlus Settings 2 (25A)
Functional Test Report - PLL
ΔV Accuracy = ±2% or ±1V, whichever is greater.
Slip Freq Accuracy =
±0.01Hz
Min/Max Slip Accuracy =
±0.01Hz
Breaker Close Angle Accuracy =
±1°
Test
Setting
Low
Actual
High
Pass/Fail
ΔV Increasing
15% (79.67 V)
78.67 V
80.67 V
P / F
ΔV Decreasing
15% (58.89 V)
57.89 V
59.89 V
P / F
Slip Freq
Increasing
0.5 Hz
60.49 Hz
60.51 Hz
P / F
Slip Freq
Decreasing
0.5 Hz
59.49 Hz
59.51 Hz
P / F
Breaker Close
Angle
Increasing (A
Φ)
20
°
19
°
21
°
P / F
Breaker Close
Angle
Decreasing
(A
Φ)
20
°
–19°
–21°
P / F
Synchronizer (25A) Test
BE1-11g