beautypg.com

Functional test report - pll – Basler Electric BE1-11g User Manual

Page 530

background image

518

9424200994 Rev N

Figure 316. BESTlogicPlus Settings 2 (25A)

Functional Test Report - PLL

ΔV Accuracy = ±2% or ±1V, whichever is greater.

Slip Freq Accuracy =

±0.01Hz

Min/Max Slip Accuracy =

±0.01Hz

Breaker Close Angle Accuracy =

±1°

Test

Setting

Low

Actual

High

Pass/Fail

ΔV Increasing

15% (79.67 V)

78.67 V

80.67 V

P / F

ΔV Decreasing

15% (58.89 V)

57.89 V

59.89 V

P / F

Slip Freq

Increasing

0.5 Hz

60.49 Hz

60.51 Hz

P / F

Slip Freq

Decreasing

0.5 Hz

59.49 Hz

59.51 Hz

P / F

Breaker Close

Angle

Increasing (A

Φ)

20

°

19

°

21

°

P / F

Breaker Close

Angle

Decreasing

(A

Φ)

20

°

–19°

–21°

P / F

Synchronizer (25A) Test