Table 116 – Basler Electric BE1-11g User Manual
Page 365

9424200994 Rev N
353
Table 115. CT Input Circuit Settings for Non-transformer or Wye-only Application
Transformer
Connection
CT Input
Connection
BE1-11g Settings
Compensation Applied
TX
CT
Phase
Rotation
N/A
WYE
NA
WYE
WYE
NONE
DAB
NA
DAB
WYE
NONE
DAC
NA
DAC
WYE
NONE
All WYE
∗
All WYE
∗
WYE
WYE
WYE
NONE
∗ Special case where all transformer windings and all CTs are connected in wye.
Table 116. CT Input Circuit Settings 1 for Delta/Wye Circuit Applications
Transformer
Connection
CT Input
Connection
BE1-11g Settings
Compensation Applied
TX
CT
Phase
Rotation
WYE
WYE
WYE
WYE
DAB for DAB
connections
DAC for DAC
connections
NONE
WYE
DAB
WYE
DAB
WYE
NONE
WYE
DAC
WYE
DAC
WYE
NONE
DAB
WYE
DAB
WYE
WYE
NONE
DAC
WYE
DAC
WYE
WYE
NONE
ZAB
WYE
ZAB
WYE
WYE
NONE
BE1-11g