Frequency Raise/Lower Continuous Output Verification

Step 1: Use BESTCOMSPlus to monitor the status of OUT2 (Lower) and OUT3 (Raise).

Step 2: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11g terminals C13

(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn,

∠0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). OUT2 and OUT3

should be open.

Step 3: Slowly increase the frequency of the phase voltage source until OUT2 closes continuously. This

should occur when the source is raised past the Min Slip setting (approximately 60.2 Hz).

Step 4: Decrease the frequency phase voltage source until OUT2 opens.

Step 5: Slowly decrease the frequency of the phase voltage source until OUT3 closes. This should

occur when the source is lowered past the Min Slip setting (approximately 59.8 Hz).

Step 6: (Optional.) Repeat steps 2 through 5 for settings group 1, 2, and 3.

Breaker Close Attempts/Sync Fail Activation Delay Verification

Step 1: Use BESTCOMSPlus to verify the settings in Table 235 to the BE1-11g and set the logic in

Figure 316.

Table 235. Sync Fail Settings PLL (25A)

Setting

Value

BESTCOMSPlus

Screen

Description

Breaker Close
Attempts

3

Control, Synchronizer
(25A)

Sets the maximum number of allowable
breaker close attempts to 3

Sync Fail Activation
Delay (s)

5

Control, Synchronizer
(25A)

Sets the activation delay for the sync fail
alarm to 5 seconds

Step 2: Prepare to monitor the status of OUT1 (Close Breaker) and OUT8 (Sync Fail).

Step 3: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11g terminals C13

(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn,

∠0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). OUT1 and OUT8

should remain open.

Step 4: Apply contact sensing voltage to B3 (IN2+) and B4 (IN2-) to initiate a close attempt and cause

OUT1 to close. CAUTION: Applying voltage above the capabilities of the equipped power
supply could cause irreversible damage to the BE1-11g. Consult the

Specifications

chapter for

more information on contact input voltage ranges.

Step 5: OUT1 should make a total of three close attempts. OUT8 should close approximately 5 seconds

after the third close attempt.

Step 6: (Optional.) Repeat steps 2 through 5 for settings group 1, 2, and 3.

BE1-11g

Synchronizer (25A) Test