536
9424200994 Rev N
Note
The 43-1 switch action is performed three times in this test. Follow the
timing sequence to illustrate timer mode action. The time delay
settings can be increased if difficulty is encountered with repeating the
43-1 switch actions.
Step 3: Use the Metering Explorer of BESTCOMSPlus to open the Control, Virtual Switches tree branch
(Figure 322). Using select-before-operate, perform the following steps to control a virtual switch.
Step 4: Click the 43-1 button to select it. Login may be required. The On or Off indicator (current state)
will begin to flash.
Note
If step 5 is not performed within 25 seconds of step 4, the indicator will
stop flashing and the 43-1 button will have to be selected again.
Step 5: Click on the 43-1 button a second time to operate it. After clicking Yes, the On or Off indicator
(previous state) will stop flashing and the On or Off indicator (current/new state) will light.
Step 6: Wait no longer than 10 seconds to interrupt time delay 1.
Step 7: Repeat steps 4 and 5 to change the state of the 43-1 switch to OFF and remove the initiate
input from the 62-1 timer.
Step 8: Wait at least 5 seconds for time delay 2 to reset.
Step 9: Repeat steps 4 and 5 to change the state of the 43-1 switch to OFF and remove the initiate
input from the 62-1 timer.
Step 10: Use the Metering Explorer in BESTCOMSPlus to open the Reports, Sequence of Events
screen. Verify that the 62-1 timer output remained false between the first 43-1 switch action
(ON) and the second 43-1 switch action (ON), the 62-1 timer output went true after the second
43-1 switch action (ON), and the 62-1 timer output returned to an OFF state.
Figure 326 illustrates the timing relationship of the 43-1 switch and 62-1 timer.
Step 11: (Optional.) Repeat steps 1 through 10 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, and 62-8.
Step 12: (Optional.) Repeat steps 1 through 11 for settings group 1, 2, and 3.
Logic Timers (62) Test