Email setup, Bestlogic™plus settings for email – Basler Electric BE1-11g User Manual
Page 332
320
9424200994 Rev N
Note
The PC running BESTCOMSPlus software must be configured
correctly to communicate with the BE1-11g. The PC must have an IP
address in the same subnet range as the BE1-11g if the BE1-11g is
operating on a private, local network.
Otherwise, the PC must have a valid IP address with access to the
network and the BE1-11g must be connected to a properly configured
router. The network settings of the PC depend on the operating
system installed. Refer to the operating system manual for
instructions.
On most Microsoft Windows based PCs, the network settings can be
accessed through the Network Connections icon located inside the
Control Panel.
8.
Click the Send to Device button located on the Configure Ethernet Port screen. A confirmation pop-up
will indicate that the BE1-11g will reboot after settings are sent. Click the Yes button to allow settings
to be sent. After the unit has rebooted and the power-up sequence is complete, the BE1-11g is ready
to be used on a network.
9.
If desired, BE1-11g settings can be verified by selecting Download Settings and Logic from the
Communication pull-down menu. Active settings will be downloaded from the BE1-11g. Verify that the
downloaded settings match the previously sent settings.
Email Setup
The BE1-11g is capable of sending email alerts when triggered by chosen logic. A maximum of eight
circumstances can be established for sending email alerts. Setup of email notifications is made on the
BESTCOMSPlus Email Setup screen (Settings Explorer, Communications, Email Setup) illustrated in
Figure 243. A notification is configured by entering the SMTP email server address and the email
addresses of the intended recipients. One email address can be entered in the “To” field and one email
address can be entered in the “Cc” field. The “Subject” field accepts up to 64 characters for describing the
condition triggering the notification email.
Figure 243. Email Setup Screen
BESTlogic
™Plus Settings for Email
BESTlogicPlus settings are made using BESTCOMSPlus. To program the BESTlogicPlus settings, use
the Settings Explorer within BESTCOMSPlus to open the BESTlogicPlus Programmable Logic tree
branch and select the email logic block from the list of Elements. The email logic block is shown in Figure
Communication
BE1-11g