156

9424200994 Rev N

Figure 97. Synchronizer Element Logic Block

Table 59. Logic Inputs and Outputs

Name

Logic

Function

Purpose

Block

Input

Disables the 25A function when true. A pulse will stop and reset the 25A
function. Also, resets the element after a sync fail.

Initiate

Input

A pulse true initiates the synchronization process. It does not have to be
maintained to continue synchronization. If it is maintained and a sync fail
occurs, the element will not be blocked, but continue with a new sync
cycle.

Status

Output

True when the synchronization criteria is met.

Close

Breaker

Output

Signals the breaker to close. True after the Status output becomes true.

Volt Monitor

Output

True when the voltage monitor settings are met.

Lower

Frequency

Output

True when the 25A element is decreasing frequency.

Raise

Frequency

Output

True when the 25A element is raising frequency.

Lower

Voltage

Output

True when the 25A element is decreasing voltage.

Raise

Voltage

Output

True when the 25A element is increasing voltage.

Sync In

Progress

Output

True when the 25A has been initiated, and is not inhibited. The 25A is
inhibited when the generator or bus voltage is less than 10 V or 15 Hz.

Sync Fail

Output

A one-cycle pulse, true when the breaker is still open after maximum
close attempts.

Volt Synced

Output

True when the voltage magnitude between sources is less than or equal
to the Voltage Difference setting. If the Voltage Source > Voltage
Destination setting is enabled, the generator voltage must be at least
0.5% greater than the bus voltage.

Synchronizer (25A)

BE1-11g