beautypg.com

Relay trouble alarm disable – Basler Electric BE1-11g User Manual

Page 50

background image

38

9424200994 Rev N

BESTlogicPlus expressions for OUT1 through OUT8 and OUTA drive contact outputs OUT1 through
OUT8 and OUTA. The state of the contact outputs can vary from the state of the output logic expressions
for three reasons:

1.

The relay trouble alarm disables all hardware outputs.

2.

The programmable hold timer is active.

3.

The select-before-operate function overrides a virtual output.

Figure 31 shows a diagram of the contact output logic for the general-purpose contact outputs. The OUT1
relay closes when the 50-1 element is in a trip condition.

Figure 31. Output Logic, General Purpose Contact Outputs

Figure 32 illustrates the contact output logic for the failsafe alarm contact output when OUTA is normally
closed (style xxxxxxx2xxxxxx). The OUTA relay closes when the 50-1 element is in a trip condition.

Figure 32. Output Logic, Failsafe Alarm Contact Output

Relay Trouble Alarm Disable

All internal circuitry and software that affects how the BE1-11g functions is monitored by the continuous
self-test diagnostics function of the relay trouble alarms. A detailed list of relay trouble alarms is provided
in Table 7. If any one of these points asserts, the failsafe alarm output relay de-energizes and
closes/opens (depending on style number) the OUTA contact, the front-panel Relay Trouble LED lights,
all output relays are disabled, logic OUTA is set, and the BE1-11g is taken offline. The relay trouble
alarms function is not programmable.

Table 7. Relay Trouble Alarms

Name

Description

NVMH Settings File Not Opened

Error opening settings file

Update NVM Blocks Failed

Error writing settings file

NVMH Saving Blocks Error

Error writing settings file

NVMH Flash File Error

Error writing settings file

Flash Error

Flash file system error

uP Reset

Repetitive reboot

Cal Error

Calibration error

Cal Defaults Loaded

BE1-11g not calibrated

Defaults Loaded

Defaults have been loaded

uP Overload

Microprocessor is busy

Power Supply

Input power is too low/failed

Contact Inputs and Outputs

BE1-11g