9424200994 Rev N

405

Timing Verification (V1 Mode)

Time Delay Range = 50 to 600,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,968 ms

2,032 ms

P / F

5

5,000 ms

4,968 ms

5,032 ms

P / F

5

10,000 ms

9,950 ms

10,050 ms

P / F

Pickup Verification (V2 Mode)

Pickup Setting Range = 1 to 150 V

Pickup Accuracy =

±2% or ±1 V, whichever is greater

Reset/Pickup Ratio = 102%

±1%

Step

Pickup

Setting

Low

Actual

Pickup

High

Low

*

Actual

Reset

High

*

Pass/Fail

V1

VA

V1

VA

V1

VA

V1

VA

V1

VA

6

78.0

234.0 76.4 229.2

79.5 238.5 78.7 236.1

80.3 240.9

P / F

7

38.0

114.0 37.0 111.0

39.0 117.0 38.3 114.9

39.1 117.3

P / F

7

22.0

66.0

21.0

63.0

23.0

69.0

22.2

66.6

22.6

67.8

P / F

* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.

Timing Verification (V2 Mode)

Time Delay Range = 50 to 600,000 ms

Timing Accuracy =

±0.5% or ±2 cycles, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,968 ms

2,032 ms

P / F

5

5,000 ms

4,968 ms

5,032 ms

P / F

5

10,000 ms

9,950 ms

10,050 ms

P / F

Pickup Verification (Vx Fundamental Mode)

Pickup Setting Range = 1 to 150 V

Pickup Accuracy =

±2% or ±1 V, whichever is greater

Reset/Pickup Ratio = 102%

±1%

Step

Pickup Setting

Low

Actual Pickup

High

Low

*

Actual Reset

High

*

Pass/Fail

6

115.0 V

112.7 V

117.3 V

116.1 V

118.4 V

P / F

7

65.0 V

63.7 V

66.3 V

65.6 V

66.9 V

P / F

7

20.0 V

19.0 V

21.0 V

20.2 V

20.6 V

P / F

* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.

BE1-11g

Auxiliary Undervoltage (27X) Test