beautypg.com

Logic connections, Operational settings – Basler Electric BE1-11g User Manual

Page 64

background image

52

9424200994 Rev N

If the 60FL element trip logic is true and Block Phase/V1 is enabled, all functions that use the phase
voltage are blocked. See the Fuse Loss (60FL) chapter for more information on the 60FL functions.

Protective elements blocked by 60FL should be set so that trip times are 60 milliseconds or greater to
assure proper coordination of blocking.

Block Logic Input

The Block input provides logic-supervision control of the element. When true, the Block input disables the
element by forcing the element outputs to logic 0. Connect the element Block input to the desired logic in
BESTlogicPlus. When the element is initially selected from the Elements view, the default condition of the
Block input is a logic 0.

Logic Connections

Sync-check element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The
sync-check element logic block is illustrated in Figure 42. Logic inputs and outputs are summarized in
Table 12.

Figure 42. Sync-Check Element Logic Block

Table 12. Logic Inputs and Outputs

Name

Logic

Function

Purpose

Block

Input

Disables the 25 function when true

Sync

Output

True when the monitored voltage between the sources meets angle,
voltage, and slip criteria

Volt Monitor

Output

True when the bus and/or line is dead

Volt Synced

Output

True when the voltage magnitude between sources is less than setting

Angle

Synced

Output

True when the phase angle between sources is less than the Slip
Angle setting

Slip Synced

Output

True when the frequency error between sources is less than the Slip
Frequency setting

Operational Settings

Sync-check element operational settings are configured on the Sync-Check (25) settings screen (Figure
43)
in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 13.

Sync-Check (25) Protection

BE1-11g