beautypg.com

Breaker close angle verification, Voltage source > voltage destination verification, Voltage raise/lower continuous output verification – Basler Electric BE1-11g User Manual

Page 528

background image

516

9424200994 Rev N

voltage of 69.28 Vpn,

∠0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). The 25A Slip Diff

digital point should be true.

Step 3: Slowly increase the frequency of the phase voltage source until the 25A Slip Diff digital point

turns off. This should occur at 60.506 Hz

±0.01 Hz. Record the results.

Step 4: Decrease the frequency of the phase voltage source until the 25A Slip Diff digital point turns on.

Step 5: Slowly decrease the frequency of the phase voltage source until the 25A Slip Diff digital point

turns off. This should happen at 59.494 Hz

±0.01 Hz.

Step 6: (Optional.) Repeat steps 2 through 5 for settings group 1, 2, and 3.

Breaker Close Angle Verification

Step 1: Use BESTCOMSPlus to monitor the status of OUT6 or the 25A Angle Diff digital point in

Metering Explorer, Status, Digital Points (1536-1567).

Step 2: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11g terminals C13

(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn,

∠0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). OUT6 should

close and the 25A Angle Diff digital point should light.

Step 3: Slowly increase the angle of the phase voltage source until OUT6 opens or the 25A Angle Diff

digital point turns off. For phase A, this should occur at +20.1

° ±1°. Record the result.

Step 4: Decrease the angle of the phase voltage source until OUT6 closes or the 25A Angle Diff turns

on.

Step 5: Slowly decrease the angle of the phase voltage source until the 25A Angle Diff turns off. For

phase A, this should occur at

–20.1° ±1°. Record the result.

Step 6: (Optional.) Repeat steps 2 through 5 for settings group 1, 2, and 3.

Voltage Source > Voltage Destination Verification

Step 1: Use BESTCOMSPlus to monitor the status of OUT6.

Step 2: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11g terminals C13

(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn,

∠0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). OUT6 should

remain open.

Step 3: Slowly increase the phase voltage source until OUT6 closes. This should occur at 69.28 V +

(0.5% = 69.63 V)

±1 V.

Step 4: (Optional.) Repeat steps 2 and 3 for settings group 1, 2, and 3.

Voltage Raise/Lower Continuous Output Verification

Step 1: Use BESTCOMSPlus to monitor the status of OUT4 (Lower) and OUT5 (Raise).

Step 2: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11g terminals C13

(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn,

∠0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). OUT4 and OUT5

should be open.

Step 3: Slowly increase the phase voltage source until OUT4 closes continuously. This should occur

when the source differs from the

ΔV setting by 1% (approximately 69.98 V ±1 V).

Step 4: Decrease the phase voltage source until OUT4 opens.

Step 5: Slowly decrease the phase voltage source until OUT5 closes. This should occur when the

source differs from the

ΔV setting by 1% (approximately 68.58 V ±1 V).

Step 6: (Optional.) Repeat steps 2 through 5 for settings group 1, 2, and 3.

Synchronizer (25A) Test

BE1-11g