Functional test report, Pickup verification table 2 row 1, Pickup verification table 2 row 2 – Basler Electric BE1-11g User Manual
Page 515: Pickup verification table 2 row 3, Timing verification

9424200994 Rev N
503
Step 4: Gradually decrease the magnitude all three phase voltages until OUT2 closes. Record the time
to trip (OUT1 closes). Verify that the 21-1-AB, 21-1-BC, and 21-1-CA targets are displayed on
the front-panel display. Increase the voltage until OUT2 opens. Reset the target.
Step 5:
Repeat step 4 for the time delays in the second and third rows of Table 231. Record the results.
Timing accuracy is 0.5% or 2 cycles, whichever is greater.
Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.
Step 7: (Optional.) Repeat steps 1 through 6 for 21-2.
Functional Test Report
Pickup Verification Table 2 Row 1
Diameter Setting Range = 0 – 500 secondary
Ω
Pickup Accuracy =
±2% or ±0.1 Ω, whichever is greater
Reset Hysteresis = 105% of the diameter setting
Reset Accuracy =
±2% or ±0.1 Ω, whichever is greater
Step
Pickup Setting
Low
Actual Pickup
High
Low
Actual Reset
High
Pass/Fail
6
45.28 Vpn
43.71 V
46.85 V
46.26 V
48.15 V
P / F
Pickup Verification Table 2 Row 2
Step
Pickup Setting
Low
Actual Pickup
High
Low
Actual Reset
High
Pass/Fail
6
42.71 Vpn
41.23 V
44.19 V
48.72 V
50.44 V
P / F
Pickup Verification Table 2 Row 3
Step
Pickup Setting
Low
Actual Pickup
High
Low
Actual Reset
High
Pass/Fail
6
4.34 Vpn
3.84 V
4.84 V
5.86 V
7.59 V
P / F
Timing Verification
Time Delay Range = 0 to 300,000 ms
Timing Accuracy =
±0.5% or ±2 cycles, whichever is greater
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
100 ms
83.3 ms
117 ms
P / F
5
60,000 ms
57,000 ms
63,000 ms
P / F
5
0 ms
>0 ms
33.3 ms
P / F
BE1-11g
Distance (21) Test