Oscillator mode, Integrating timer mode, Figure 325 – Basler Electric BE1-11g User Manual
Page 547: Block initiate 62-x
9424200994 Rev N
535
Note
The 43-1 switch action is performed three times in this test. To
illustrate the action of the timer mode, step 4 should be executed as
quickly as possible for the second 43-1 switch action (within 15
second duration of the pickup time delay). Perform step 4 again for the
third 43-1 switch action after at least 15 seconds (the pickup timer
setting) have elapsed but before the 20 second dropout time delay
expires. This will illustrate the action of the timer mode. The time delay
settings can be increased if difficulty is encountered with repeating the
43-1 switch actions.
Figure 325. One-Shot/Retriggerable Mode
Step 8: (Optional.) Repeat steps 1 through 7 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, and 62-8.
Step 9: (Optional.) Repeat steps 1 through 8 for settings group 1, 2, and 3.
Oscillator Mode
Because this operating mode is not intended for general use, no testing procedure is available.
Information about Oscillator mode is available in the
chapter.
Integrating Timer Mode
Step 1: Use BESTCOMSPlus to send the operational settings in Table 244 to the BE1-11g. Retain the
logic settings from Figure 321.
Table 244. Operational Settings (Integrating Timer Mode)
Setting
Value
BESTCOMSPlus Screen
Description
62-1 Mode
Integrating
Timer
Control, Logic Timers (62)
Sets 62-1 to Integrating Timer
mode
62-1 Time Delay 1
(T1)
15,000 ms
Control, Logic Timers (62)
Sets 62-1 pickup time delay to
15,000 ms
62-1 Time Delay 2
(T2)
5,000 ms
Control, Logic Timers (62)
Sets 62-1 dropout time delay to
5,000 ms
43-1 Mode
Switch
Control, Virtual Control
Switches (43)
Sets 43-1 to Switch mode
62-1 Target
Enabled
Target Configuration, Targets
screen.
Enables 62-1 target
Step 2: Steps 3 through 5 supply the 62-1 timer with a block input by changing the 43-1 switch state to
ON. You can view the state changes of the 43-1 switch at the Metering > Control > Virtual
Switches screen on the front-panel display.
P
0
0
3
5
-3
2
0
2
-2
7
-0
6
Block
Initiate
62-x
BE1-11g
Logic Timers (62) Test