Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the
Elements view, the default condition of the Block input is a logic 0.

Logic Connections

Logic timer element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The
logic timer element logic block is illustrated in Figure 108. Logic inputs and outputs are summarized in
Table 63.

Figure 108. Logic Timer Element Logic Block

Table 63. Logic Inputs and Outputs

Name

Logic Function

Purpose

Initiate

Input

Starts the 62 timing sequence

Block

Input

Disables the 62 function when true

Output

Output

True when 62 timing criteria have been met according to mode

Operational Settings

Logic timer element operational settings are configured on the Logic Timers (62) settings screen (Figure
109)
in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 64.

Figure 109. Logic Timers Settings Screen

Logic Timers (62)